Operation Summer
Operation
Summer cycle
In summer operation, the 4-way valve is activated.
The circuit followed by the refrigerant is shown in the relevant
diagram.
Winter cycle
In the winter cycle, the discharge gas goes to the indoor
coil, which acts as the condenser. The outdoor coil becomes
the evaporator. The 4-way valve is not activated. The
circuit followed by the refrigerant is shown in the relevant diagram.
Operating sequences (See relevant wiring diagrams)
Summer cycle:
Thermostat in COOL position
1) The 4-way valve is activated through the thermostat,
permitting the refrigerant to circulate in the summer
circuit.
2) If the fan operating mode in the ambient thermostat is in
FAN ON, the contactor is activated and the fan functions
continuously.
3) With the logic module timing, the unit will start up after 5
minutes.
4) When the thermostat contact connects, the contactor is
activated and the compressor starts up. If the fan operating
mode is in the normal position, the contactor is
activated through the thermostat's cooling circuit and the
fan starts up.
5) The unit will function intermittently in response to the